Circuit Breaker Size Calculator

This free breaker size calculator answers the second half of every circuit question: once you know the load, which standard breaker protects it? It converts watts to amps when that is what the nameplate gives you, applies the 125% rule for continuous loads like EV charging (NEC 210.20(A)), and rounds up to the next standard rating from Table 240.6(A) — never down.

It is equally honest about what a breaker calculator must NOT do: motor, HVAC, and welder circuits are sized from the equipment nameplate under their own code articles, where a breaker larger than the wire ampacity can be legal and correct. Pick the motor/HVAC load type and the calculator explains that path instead of guessing at it.

The breaker is only half the pairing — the conductor must be rated for it, including the small-conductor caps of 240.4(D) that limit 14, 12, and 10 AWG regardless of what the ampacity chart says. Every result links to the wire size calculator to complete the pair. Reference only: verify with a licensed electrician and your local AHJ. Free, no signup.

View material estimation guides →

Breaker Size Calculator

What size breaker for your load? Enter amps or watts, mark continuous loads, and get the minimum standard breaker per NEC 240.6(A) with the 125% rule applied — plus the wire rating it must pair with. Free, no signup.

Load

Continuous = runs at max current 3+ hours (EV charging is the classic case) — the code requires 125% sizing. Motor/HVAC/welder circuits follow their nameplate, not the generic rules.

Plan disposal before you start

Smaller jobs still produce more debris than a few trash bags can hold. Check what's allowed in a dumpster and which disposal option fits the scope.

See disposal options →

Related Calculators

Explore Electrical: calculators, diagrams & guidesEvery calculator, cross-section diagram, and guide for this trade in one place.

How to Use This Calculator

  1. Enter the load — amps directly, or watts plus voltage if that is what the nameplate shows.
  2. Choose the load type: non-continuous for typical appliances, continuous for anything running 3+ hours at full current (EV charging is the classic case), or motor/HVAC/welder to see why the nameplate governs those.
  3. Click Calculate for the minimum standard breaker (NEC 240.6(A)), the required capacity behind it, and the conductor rating it must pair with.
  4. Size the wire to match with the wire size calculator — breaker and conductor are one decision, not two.

Why Breakers Round Up — and When They May Not

Breakers come in standard ratings (15, 20, 25, 30, 35, 40, 45, 50, 60 and up per NEC Table 240.6(A)), so a 22.9 A water-heater load lands on a 25 A breaker — the next standard size. But rounding up past the CONDUCTOR's ampacity is only permitted under the three conditions of 240.4(B): the circuit can't serve multiple receptacles for portable loads, the conductor ampacity can't already match a standard rating, and the next size can't exceed 800 A. And small conductors have hard caps regardless (240.4(D)): 14 AWG copper stops at 15 A, 12 at 20 A, 10 at 30 A. The one place bigger-than-expected breakers are routinely correct: motors and HVAC, where starting current is allowed to dictate protection (up to 250% for inverse-time breakers under 430.52, or whatever the HVAC nameplate MOP says) while the wire is sized separately. That is why this calculator hands those loads to the nameplate instead of computing them.

Frequently Asked Questions

What size breaker do I need for a 4500 watt water heater?

A 4,500 W element at 240 V draws 18.75 A; a 5,500 W element draws 22.9 A. Both land on a 25 A or 30 A breaker depending on how your jurisdiction treats water heaters — many electricians size storage water heaters at 125% (which makes 4,500 W → 23.4 A → 25 A, and the common install is 30 A with 10 AWG wire). Enter your element wattage and voltage in the calculator, and confirm the load type treatment with your inspector — then pair the wire with the wire size calculator.

What are the standard breaker sizes?

Per NEC Table 240.6(A), the standard ampere ratings in the residential range are 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, and 200 A (the table continues to 6,000 A, and 1/3/6/10/601 A exist for fuses only). Your required capacity rounds UP to the next standard rating — a 22.9 A load takes a 25 A breaker, a 52 A load takes a 60 A breaker. Never round down.

When do I multiply by 125%?

When the load is continuous — expected to run at maximum current for 3 hours or more (NEC 210.20(A)). EV charging is the classic residential continuous load: a 48 A charger needs 48 × 1.25 = 60 A of protection. Most ordinary appliances — dryers, ranges, dishwashers — cycle on and off and are sized as non-continuous. When in doubt, the equipment installation manual states the required circuit, and it always governs.

Can my breaker be bigger than my wire's rating?

Almost never — and the exceptions are specific. The general rule is the conductor must be protected at or below its ampacity, with small conductors hard-capped by 240.4(D) (14 AWG Cu at 15 A, 12 at 20 A, 10 at 30 A). The 240.4(B) allowance lets you round UP to the next standard breaker only when the ampacity doesn't match a standard rating, the circuit isn't a multi-receptacle portable-load circuit, and you stay at or under 800 A. The legitimate big exception: motors and HVAC, where starting current allows oversized protection under Articles 430/440 — sized from the nameplate, not this calculator.

Why won't this size my AC or well pump breaker?

Because the code sizes those from the equipment nameplate, not from the running amps. HVAC equipment lists an MOP (Maximum Overcurrent Protection) on its nameplate — that IS the breaker answer, and under Article 440 it may exceed the wire's ampacity to ride through compressor starting current. Motor circuits similarly allow inverse-time breakers up to 250% of full-load current (430.52). Feeding those loads through the generic 125% math produces wrong (usually too-small) breakers that nuisance-trip — so the calculator routes you to the nameplate instead.