Whole-house ventilation — ASHRAE 62.2 vs the IRC give different rates for the same house

ASHRAE uses a 0.03 area coefficient, the IRC 0.01 (it assumes more natural infiltration) — 90 vs 50 CFM for the same house.

Source: ASHRAE 62.2-2019 §4.1.1 / IRC M1505.4.3
Use this diagram free on your site — grab the embed codeGet the code

What this diagram shows

A 2,000 square foot, 3-bedroom house on the left feeds two result cards. The ASHRAE 62.2-2019 card (0.03 times area plus 7.5 times bedrooms-plus-one) works out to 90 CFM and is marked the stricter. The IRC Equation 15-1 card uses 0.01 instead of 0.03 and works out to 50 CFM, marked as assuming more infiltration. Both share the same occupant term; only the floor-area coefficient differs.

Use this diagram — free

You're welcome to use this diagram on your own site, blog, handout, or lesson at no cost. The only condition is a visible credit link back to the source page. Copy the snippet below and paste it into your page — the credit is already included.

Please keep the credit link intact and don't alter the diagram itself. Redistribution as part of a competing diagram library or template pack isn't permitted. Questions? Reach us via the site.